Fire Protection

OCV RCE

Latching Relay

A pressure operated, 3/2-Way, latching manual and remote reset device, applicable for service deluge and pre-action valve trims. In its “Ready” position, the RCE latching relay prevents draining of the deluge valve’s control chamber, keeping the deluge valve closed. Once the deluge valve is actuated, the RCE latching relay shifts to its “Latched-Open” position, allowing draining of the control chamber and latching open the deluge valve. Resetting is accomplished by energizing a “Closing” solenoid valve or by manually pressing the RCE relay’s reset knob.

Technical Specifications

Size Unit

Working pressure range

PN 25

Working temperature

80°C Max

Fire Protection certifications

UL Listed

When installed on OCV valves

Material

Available in Stainless Steel 316