Fire Protection

OCV DMR

Manual Reset Latching Device

A spring-loaded, manual reset latching device, applicable for service on deluge and pre-action valve trims. In the “Ready” position, the DMR prevents draining of the deluge valve’s control chamber, keeping the deluge valve closed. Once the deluge valve is actuated, the DMR shifts to its “Latched-Open” position, allowing draining of the control chamber and latching open the deluge valve. Manual resetting is accomplished by holding the DMR’s knob until the deluge valve has closed.

Downloads

Product Page (PDF)

Technical Specifications

Size Unit

Working pressure range

PN 25

Working temperature

80°C Max

Fire Protection certifications

UL Listed

When installed on OCV valves

Body & Bonnet

Brass

Optional: Stainless Steel

Elastomers

NBR

Stem

Stainless Steel

Ball

Viton® 

Spring

Stainless Steel

This site is registered on wpml.org as a development site. Switch to a production site key to remove this banner.